0.6/1kv PVC Insulated Power Cable
 
Products Introduction:
PVC Insulated Power Cable applies to electric line at rated voltage 0.6/1KV, the mechanical performance and electric property of the cable is manufactured according to the standard of GB/T12706.1 - 2008 and IEC60502 - 1997. Flame resistant cable can be GB/T19666 - 2005.

Operating Characteristics:
1.The highest rated working temperature of PVC insulated control cable conductor is 70℃, XLPE insulated control cable conductor is 90℃.
2.Bending Radius
 The minimum bending radius of non armoured cable:Single-core cable 15D; Multiple-core cable 12D
 The minimum bending radius of armoured cable:Single-core cable 20D; Multiple-core cable 15D
 D is the diameter of the finished cable.
3.The environmental temperature for laying could not be less than 0℃, below 0℃ installation must be preheat.

Type, Designation and Main Application of Cable:

Type

Designation

Main Applications

 VV VLV  Copper(Aluminium)Conducter PVC Insulated and sheathed Power Cable
For laying indoor and outdoor tunnels, able to bear a centain traction installation, but unable to bear pulling force and pressure, single core cable can not be laid in the magnetic tube. Flame retardant, fire-resistant cable suitable for the places with higher requirements for fire protection.
 ZR-VV ZA-VV ZB-VV ZC-VV
 ZR-VLV ZA-VLV ZB-VLV ZC-VLV
 Copper(Aluminium)Conducter Flame Retardant PVC Insulated and sheathed Power Cable
 NH-VV NHZA-VV NHZB-VV
 NHZB-VV NHZC-VV
 Copper(Aluminium)Conducter Fire-resistant PVC Insulated and sheathed Power Cable
 VV22 VLV22  Copper(Aluminium)Conducter PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable For laying direct in ground, able to bear a centain traction installation, pulling force and pressure, flame retardant, fire-resistant cable suitable for the place with higher requirements for fire protection.
 ZR-VV22 ZA-VV22 ZB-VV22 ZC-VV22
 ZR-VLV22 ZA-VLV22 ZB-VLV22 ZC-VLV22
 Copper(Aluminium)Conducter Flame Retardant PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable
 NH-VV22 NHZA-VV22 NHZB-VV22
 NHZB-VV22 NHZC-VV22
 Copper(Aluminium)Conducter Fire-resistant PVC Insulated Steel Wire Armoured PVC Sheathed Power Cable

Production Range of Cable:

Type

No. of Cores

Nom. Cross-section of Conductor(mm²)
Copper Core Aluminum Core
  1 Core 1.5-630 2.5-630
 VV VLV ZR-VV ZA-VV ZB-VV ZC-VV ZR-VLV  2 Cores 1.5-400 2.5-400
 ZA-VLV ZB-VLV ZC-VLV NH-VV NHZA-VV NHZB-VV 3 Cores
 NHZC-VV VV22 VLV22 ZR-VV22 ZA-VV22 ZB-VV22  4 Cores
 ZC-VV22 ZR-VLV22 ZA-VLV22 ZB-VLV22  5 Cores
 ZC-VLV22  NH-VV22 NHZA-VV22 NHZB-VV22 3+1 Cores
 NHZC-VV22  3+2 Cores
  4+1 Cores

Main Properties of the Finished Cable Insualtion and Sheath:
Item PVC Insulation
PVC Sheath
 Tensile Strength 不小于 12.5Mpa 不小于 12.5Mpa
 Elongation at break 不小于 150% 不小于 150%
 Volume Resistivity at 70℃ 不小于1×1010Ωcm /

Main Electrical Properties of the Finished Cable:
The D.C. resistance of finished cable conductive core is not greater than the provisions of Article 5 at 20℃.
Finished cable at 3.0KV AC voltage test 5 min without breakdown.

Technical Specifications:
1.The conductor of the nominal cross section 6mm2 and below adopts single core solid conductor; the nominal cross section 10mm2 and above adopts stranded conductor. The conductor of single - core and twin - core adopt circular or round pressed core; 3, 4, 3+1 core of the nominal cross section 25mm2 and below adopt circular (round pressed) core; the nominal cross section 35mm2 and above adopt twisted round (round pressed) or sector pressed core. 5, 3+2, 4+1 core of the nominal cross section 35mm2 and below sdopt circular (round pressed) core; the nominal cross section 50mm2 and above adopt twisted round (round pressed) or tile pressed core.
2.Copper, aluminum conductive core comply with the relevant provisins of GB/T3956 - 1997.
3.The insulated material is PVC insulation and complies with the relevant provisions of GB/T12706.1 - 2008.
4.The insulation of the multi - core cable wire core should be cabling. The insulated cores comply with the table below with color recognition or digital recognition, or according to user's requirements.
No. of Cores
Color Recognition Digital Recognition Remarks
Master Core Midline Core Master Core Midline Core
1 Random Color   / / The color recognition could be manufactured according to user's requirements.
2 Red Blue 1 0
3 Red、Yellow、Green 1、2、3 /
4、3+1 Red、Yellow、Green Blue 1、2、3 0
5、3+2、4+1 Red、Yellow、Green Blue、Black(Yellow/Green) 1、2、3 4、0
5.The D.C. resistance of finished cable conductor wire core complies with the provisions of the table below.
Nom. Cross-section of Conductor(mm²) Max D.C. Resistance of Conduct 20℃.(Ω/km) Nom. Cross-section of Conductor(mm²) Max D.C. Resistance of Conduct 20℃.(Ω/km)
Copper Conductor Aluminum Conductor Copper Conductor Aluminum Conductor
1 18.1   70 0.268 0.443
1.5 12.1   95 0.193 0.320
2.5 7.41 18.1 120 0.153 0.253
4 4.61 12.1 150 0.124 0.206
6 3.08 7.41 185 0.0991 0.164
10 1.83 4.61 240 0.0754 0.125
16 1.15 1.91 300 0.0601 0.100
25 0.727 1.20 400 0.0470 0.0778
35 0.524 0.868 500 0.0366 0.0605
50 0.387 0.641 630 0.0283 0.0469
6.Flame retardant cables, fire-resisitant cables, flame resistant cable shall comply with GB/T19666 - 2005.

Main Parameter of 0.6/1KV Single - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
1×1.5 0.8 1.4 / 5.8 / 49 / / / 21 / / /
1×2.5 0.8 1.4 / 6.2 / 61 / / / 31 24 / /
1×4 1.0 1.4 / 7.1 / 85 61 / / 41 32 / /
1×6 1.0 1.4 / 7.6 / 107 73 / / 52 43 / /
1×10 1.0 1.4 / 8.8 / 155 95 / / 70 55 76 59
1×16 1.0 1.4 / 9.9 / 218 122 / / 97 73 99 77
1×25 1.2 1.4 / 11.7 / 322 172 / / 120 96 125 97
1×35 1.2 1.4 / 12.7 / 418 209 / / 150 115 150 115
1×50 1.4 1.4 / 15.6 / 569 286 / / 180 140 175 135
1×70 1.4 1.4 / 16.7 / 761 352 / / 230 180 215 165
1×95 1.6 1.5 / 18.7 / 1030 463 / / 280 215 255 200
1×120 1.6 1.5 / 21.2 / 1279 563 / / 325 255 290 225
1×150 1.8 1.6 / 22.9 / 1564 679 / / 375 290 325 255
1×185 2.0 1.6 / 24.7 / 1924 820 / / 430 335 370 285
1×240 2.2 1.7 / 28.9 / 2502 1065 / / 515 400 430 335
1×300 2.4 1.8 / 30.9 / 3109 1289 / / 595 465 485 380
1×400 2.6 1.9 / 34.7 / 3954 1607 / / 700 550 555 435
1×500 2.8 2.0 / 38.4 / 5011 2020 / / 810 640 630 495
1×630 2.8 2.2 / 42.9 / 6377 2520 / / 950 760 715 570

Main Parameter of 0.6/1KV Twin - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
2×1.5 0.8 1.8 / 10.1 / 112 / / / 18 / / /
2×2.5 0.8 1.8 / 10.9 / 139 / / / 25 19 / /
2×4 1.0 1.8 1.8 12.7 16.5 191 143 313 266 33 26 / /
2×6 1.0 1.8 1.8 13.7 17.5 238 169 370 301 42 34 / /
2×10 1.0 1.8 1.8 16.1 20.0 339 218 495 375 58 44 84 65
2×16 1.0 1.8 1.8 18.1 22.2 467 276 647 456 76 59 110 85
2×25 1.2 1.8 1.8 21.5 25.7 683 383 897 597 98 76 140 110
2×35 1.2 1.8 1.8 23.9 27.8 882 464 1113 695 120 93 175 135
2×50 1.4 1.8 1.8 27.5 33.6 1177 611 1483 917 145 115 205 160
2×70 1.4 1.9 1.9 31.1 35.9 1592 774 1909 1091 185 145 255 195
2×95 1.6 2.0 2.1 35.7 42.6 2146 1012 2858 1724 230 170 305 235
2×120 1.6 2.1 2.2 38.9 47.8 2656 1223 3489 2056 265 205 350 270
2×150 1.8 2.2 2.4 43.5 51.1 3248 1478 4150 2380 305 235 390 305
2×185 2.0 2.4 2.5 48.1 55.0 4029 1822 4981 2773 350 275 440 345
2×240 2.2 2.6 2.7 54.1 63.3 5215 2340 6355 3480 420 330 495 400
2×300 2.4 2.7 2.9 60.1 67.4 6469 2829 7690 4050 480 380 565 455
2×400 2.6 3.0 3.1 68.1 74.9 8256 3562 9591 4897 580 445 660 530

Main Parameter of 0.6/1KV Three - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
3×1.5 0.8 1.8 / 10.6 / 138 / / / 15 / / /
3×2.5 0.8 1.8 / 11.4 / 173 / / / 21 17 / /
3×4 1.0 1.8 1.8 13.4 17.2 246 174 375 303 28 22 / /
3×6 1.0 1.8 1.8 14.5 18.3 312 209 452 349 36 29 / /
3×10 1.0 1.8 1.8 17.1 20.9 456 275 621 440 49 38 72 55
3×16 1.0 1.8 1.8 19.2 23.3 640 354 831 545 66 51 94 73
3×25 1.2 1.8 1.8 22.9 27.1 952 502 1180 730 84 65 120 94
3×35 1.2 1.8 1.8 21.1 25.0 1208 581 1409 782 100 80 145 110
3×50 1.4 1.8 1.9 24.7 28.8 1638 789 1884 1035 125 98 175 135
3×70 1.4 1.9 2.0 27.8 31.9 2233 1006 2509 1282 160 120 210 165
3×95 1.6 2.0 2.2 31.8 38.7 3032 1330 3670 1969 195 150 255 200
3×120 1.6 2.1 2.3 34.8 41.7 3772 1622 4468 2318 235 180 295 230
3×150 1.8 2.3 2.5 39.4 46.3 4644 1989 5428 2773 260 200 330 255
3×185 2.0 2.4 2.6 43.4 50.3 5749 2437 6609 3297 305 235 370 290
3×240 2.2 2.6 2.8 48.9 55.8 7465 3153 8429 4116 360 280 425 335
3×300 2.4 2.8 3.0 53.7 60.6 9305 3845 10360 4900 410 320 480 375
3×400 2.6 3.1 3.3 59.4 66.3 11860 4819 13021 5980 485 380 555 435

Main Parameter of 0.6/1KV Four - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
4×1.5 0.8 1.8 1.8 11.4 / 165 / / / 15 / / /
4×2.5 0.8 1.8 1.8 12.3 / 212 / 316 / 21 17 / /
4×4 1.0 1.8 1.8 14.5 16.3 304 209 427 332 28 22 / /
4×6 1.0 1.8 1.8 15.7 17.5 391 253 526 389 36 29 / /
4×10 1.0 1.8 1.8 18.6 20.5 577 336 741 500 49 38 72 55
4×16 1.0 1.8 1.8 21.0 23.2 819 438 1012 631 66 51 94 73
4×25 1.2 1.8 1.8 25.2 27.4 1229 629 1463 862 84 65 120 94
4×35 1.2 1.7 1.9 24.0 26.3 1571 735 1807 971 100 80 145 110
4×50 1.4 1.9 2.0 27.9 30.0 2158 1025 2415 1283 125 98 175 135
4×70 1.4 2.0 2.2 31.7 36.0 2947 1311 3557 1921 160 120 210 165
4×95 1.6 2.1 2.4 36.7 41.2 4010 1741 4734 2465 195 150 255 200
4×120 1.6 2.3 2.5 40.2 44.5 5007 2141 5776 2910 235 180 295 230
4×150 1.8 2.4 2.6 44.3 48.7 6129 2589 6978 3439 260 200 330 255
4×185 2.0 2.6 2.8 48.9 53.2 7612 3197 8543 4128 305 235 370 290
4×240 2.2 2.8 3.0 54.6 58.9 9879 4129 10913 5163 360 280 425 335
4×300 2.4 3.0 3.2 59.6 63.9 12311 5030 13436 6156 410 320 480 375
4×400 2.6 3.3 3.5 65.7 71.2 15687 6299 17532 8144 485 380 555 435

Main Parameter of 0.6/1KV Five - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
5×1.5 0.8 1.8 / 12.2 / 193 / / / 15 / / /
5×2.5 0.8 1.8 1.8 13.3 15.1 251 / 363 / 21 17 / /
5×4 1.0 1.8 1.8 15.7 17.5 363 244 498 379 28 22 / /
5×6 1.0 1.8 1.8 17.1 18.9 471 299 618 447 36 29 / /
5×10 1.0 1.8 1.8 20.3 22.2 700 398 880 579 49 38 72 55
5×16 1.0 1.8 1.8 23 25.2 1000 524 1212 736 66 51 94 73
5×25 1.2 1.7 1.8 27.4 29.9 1495 744 1765 1015 84 65 120 94
5×35 1.2 1.8 2 30.7 33.1 1979 934 2291 1246 100 80 145 110
5×50 1.4 2 2.2 31.7 36.0 2689 1274 3294 1879 125 98 175 135
5×70 1.4 2.1 2.3 36.7 41.0 3680 1635 4381 2337 160 120 210 165
5×95 1.6 2.3 2.5 40.2 44.5 4999 2163 5762 2926 195 150 255 200
5×120 1.6 2.4 2.6 44.3 48.6 6224 2642 7064 3481 235 180 295 230
5×150 1.8 2.6 2.8 48.9 53.2 7642 3217 8565 4140 260 200 330 255
5×185 2.0 2.8 3 54.6 58.9 9497 3978 10524 5004 305 235 370 290
5×240 2.2 3 3.2 59.6 63.9 12305 5118 13417 6229 360 280 425 335
5×300 2.4 3.2 3.5 65.5 70.0 15340 6240 16590 7489 410 320 480 375
5×400 2.6 3.6 3.8 71.7 77.3 19566 7831 21556 9821 485 380 555 435

Main Parameter of 0.6/1KV 3+1 - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
3×1.5+1×1 0.8 1.8 1.8 10.6 / / / / / 15 / / /
3×2.5+1×1.5 0.8 1.8 1.8 11.0 / / / / / 21 17 / /
3×4+1×2.5 1.0 1.8 1.8 14.0 15.9 287 200 404 317 28 22 / /
3×6+1×4 1.0 1.8 1.8 15.5 17.4 372 245 507 380 36 29 / /
3×10+1×6 1.0 1.8 1.8 17.6 19.4 534 318 687 472 49 38 72 55
3×16+1×10 1.0 1.8 1.8 19.9 21.8 759 413 936 590 66 51 94 73
3×25+1×16 1.2 1.8 1.8 23.5 25.4 1135 590 1339 793 84 65 120 94
3×35+1×16 1.2 1.8 1.8 23.4 25.3 1401 679 1604 882 100 80 145 110
3×50+1×25 1.4 1.8 1.9 27.3 29.4 1917 918 2178 1179 125 98 175 135
3×70+1×35 1.4 1.9 2.1 30.6 32.9 2622 1187 2930 1495 160 120 210 165
3×95+1×50 1.6 2.1 2.3 35.5 37.8 3557 1573 3915 1930 195 150 255 200
3×120+1×70 1.6 2.2 2.4 38.8 42.3 4504 1945 5252 2694 235 180 295 230
3×150+1×70 1.8 2.3 2.5 42.9 46.4 5356 2293 6185 3121 260 200 330 255
3×185+1×95 2.0 2.5 2.7 47.4 50.9 6729 2850 7643 3764 305 235 370 290
3×240+1×120 2.2 2.7 2.9 53.1 56.6 8688 3659 9711 4682 360 280 425 335
3×300+1×150 2.4 2.9 3.1 58.0 61.5 10802 4457 11918 5573 410 320 480 375
3×400+1×185 2.6 3.1 3.3 63.8 68.5 13706 5561 15530 7385 485 380 555 435

Main Parameter of 0.6/1KV 3+2 - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
3×1.5+2×1 0.8 1.8 1.8 11.6 / 177 / / / 15 / / /
3×2.5+2×1.5 0.8 1.8 1.8 13.4 / 235 / / / 21 17 / /
3×4+2×2.5 1.0 1.8 1.8 14.9 17.3 330 229 460 359 28 22 / /
3×6+2×4 1.0 1.8 1.8 16.7 18.9 434 283 585 434 36 29 / /
3×10+2×6 1.0 1.8 1.8 18.9 22.2 618 369 811 561 49 38 72 55
3×16+2×10 1.0 1.8 1.8 21.6 25.2 887 481 1111 705 66 51 94 73
3×25+2×16 1.2 1.8 1.8 25.3 29.7 1328 688 1586 946 84 65 120 94
3×35+2×16 1.2 1.8 1.9 27.3 32.1 1612 795 1909 1092 100 80 145 110
3×50+2×25 1.4 1.9 2.0 31.7 39.4 2229 1079 2641 1492 125 98 175 135
3×70+2×35 1.4 2.0 2.2 36.7 40.7 3062 1417 3774 2130 160 120 210 165
3×95+2×50 1.6 2.2 2.3 40.2 44.0 4104 1836 4862 2594 195 150 255 200
3×120+2×70 1.6 2.3 2.5 44.5 48.3 5264 2297 6122 3155 235 180 295 230
3×150+2×70 1.8 2.4 2.6 48.9 52.7 6124 2652 7069 3596 260 200 330 255
3×185+2×95 2.0 2.6 2.8 54.6 58.4 7763 3317 8817 4371 305 235 370 290
3×240+2×120 2.2 2.8 3.0 59.6 63.4 9960 4214 11111 5365 360 280 425 335
3×300+2×150 2.4 3.0 3.2 65.5 69.3 12366 5136 13630 6400 410 320 480 375
3×400+2×185 2.6 3.2 3.5 71.5 76.2 15649 6401 17708 8460 485 380 555 435

Main Parameter of 0.6/1KV 4+1 - core PVC Insulated Power Cable:

specifi-
cation

Insulation ThickNess
(mm)

Sheath Thickness(mm) Approx. Overall Diameter of Cable (mm) Approx. Weight of Cable (kg/km) Current Rating (A)
Non Armoured Armoured Air Laying Underground Laying
Non Armoured Armoured Non Armoured Armoured Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core Copper Core Aluminum Core
4×1.5+1×1 0.8 1.8 1.8 11.5 / / / 288 / 15 / / /
4×2.5+1×1.5 0.8 1.8 1.8 12.7 / / / 355 / 21 17 / /
4×4+1×2.5 1.0 1.8 1.8 14.9 17.3 343 233 477 367 28 22 / /
4×6+1×4 1.0 1.8 1.8 16.5 18.9 449 288 601 440 36 29 / /
4×10+1×6 1.0 1.8 1.8 19.8 22.2 661 385 845 570 49 38 72 55
4×16+1×10 1.0 1.8 1.8 22.8 25.2 948 507 1161 720 66 51 94 73
4×25+1×16 1.2 1.8 1.8 27.3 29.7 1425 729 1674 978 84 65 120 94
4×35+1×16 1.2 1.8 1.9 29.5 32.1 1800 869 2085 1154 100 80 145 110
4×50+1×25 1.4 2 2.1 37 41.6 2509 1227 3230 1948 125 98 175 135
4×70+1×35 1.4 2.1 2.2 36.1 40.7 3365 1520 4067 2222 160 120 210 165
4×95+1×50 1.6 2.3 2.4 39.6 44.2 4544 1992 5310 2759 195 150 255 200
4×120+1×70 1.6 2.5 2.6 43.9 48.5 5755 2480 6603 3328 235 180 295 230
4×150+1×70 1.8 2.6 2.7 48.3 52.9 6883 2935 7815 3866 260 200 330 255
4×185+1×95 2.0 2.8 2.9 54 58.6 8629 3647 9669 4686 305 235 370 290
4×240+1×120 2.2 3 3.1 59 63.6 11128 4661 12262 5795 360 280 425 335
4×300+1×150 2.4 3.2 3.3 64.9 69.5 13847 5681 15092 6927 410 320 480 375
4×400+1×185 2.6 3.5 3.7 70.6 76.6 17592 7100 19638 9146 485 380 555 435